Cách Đấu Nối Module Giám Sát FMM-101 Notifier

Speciications- Thông số kỹ thuật
Nominal Operating Voltage: 15-32 VDC
Average Operating Current: 375µA maximum (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
EOL resistance: 47K Ohms
Maximum SLC Wiring Resistance: 40 Ohms
Maximum IDC Wiring Resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 1.3˝ H x 2.75˝ W x 0.5˝ D
Wire Length: 6˝ minimum

Before installing
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
eneral escription
The FMM-101 monitor module can be installed in a single gang junction box
directly behind the monitored unit. Its small size and light weight allow it to
be installed without rigid mounting (see Figure 1). The FMM-101 is intended
for use in intelligent, two-wire systems where the individual address of each
module is selected using rotary switches. It provides a two-wire initiating device circuit for normally open contact fire alarm and security devices. This module can be used to replace an MMX-101 module in existing systems.