GESE

Trung tâm báo cháy 5 kênh NOHMI FAPN202-R-5L

Danh mục:

Mô tả

Trung tâm báo cháy 5 kênh NOHMI FAPN202-R-5L  - On receiving a fire signal from a fire detector or a manual alarm box, the FAPN202-R-5L conventional fire alarm panel produces visual alarms to alert the alarm panel operator. It also produces alarms to alert the occupants of the building premises. The FAPN202-R-5L conventional fire alarm panel indicates the alarm points on individual zone lamps.  Features  - Conventional type 5 fire zones (No programming required).  - Alarm verification type (Alarm verification time: 60 seconds).  - Various test functions: Fire indication test, alarm verification time test, auxiliary power supply test, automatic after-test resetting.  - Self diagnosis system.  - Misoperation inhibit function.  - Back-up power supply (Ni-Cd battery, 24VDC).  - Large fire alarm symbol for easy visual recognition.  - Durable LED indicators.  - Removable front cover for easy installation and maintenance.  - Built-in surge arrester for power lines.  Đặc tính kỹ thuật  Model 	FAPN202-R-5L Type	Conventional type Power supply	220VAC 50/60Hz Auxiliary power supply	Ni-Cd battery (24VDC, 0.45Ah) Circuit voltage	5, 24, 48 VDC, 24VDC  Alarm Verification time	Thermal detector: 10 sec, Smoke detector: 60sec Power consumption	Monitoring: 25VA max. approx Alarm: 40VA max, approx Maximum number of devices supported	Spot type smoke detectors: 30/zone (max.150/panel) Alarm bells: 15 (24VDC, 10mA/bell) Location lamps: 5 (30V, 2W/lamp)  15(24V, 24mA/LED), 21 (24V, 15mA/LED) Ambient temperature and humidity	0 to 40°C, 20 to 85% (RH) Alarm input circuit loop resistance	Less than 50Ω/Loop End-of-Line resistor	10kΩ, 1/2W Materials (enclosure)	ABS resin with 94UL-V2 flammability rating Color	Off-white (Nohmi White): Approximating Munsell N8.7 or equivalent Weight	Approx. 3kgTrung tâm báo cháy 5 kênh NOHMI FAPN202-R-5L

– On receiving a fire signal from a fire detector or a manual alarm box, the FAPN202-R-5L conventional fire alarm panel produces visual alarms to alert the alarm panel operator. It also produces alarms to alert the occupants of the building premises. The FAPN202-R-5L conventional fire alarm panel indicates the alarm points on individual zone lamps.

Features

– Conventional type 5 fire zones (No programming required).

– Alarm verification type (Alarm verification time: 60 seconds).

– Various test functions: Fire indication test, alarm verification time test, auxiliary power supply test, automatic after-test resetting.

– Self diagnosis system.

– Misoperation inhibit function.

– Back-up power supply (Ni-Cd battery, 24VDC).

– Large fire alarm symbol for easy visual recognition.

– Durable LED indicators.

– Removable front cover for easy installation and maintenance.

– Built-in surge arrester for power lines.

Đặc tính kỹ thuật

Model  FAPN202-R-5L
Type Conventional type
Power supply 220VAC 50/60Hz
Auxiliary power supply Ni-Cd battery (24VDC, 0.45Ah)
Circuit voltage 5, 24, 48 VDC, 24VDC
Alarm Verification time Thermal detector: 10 sec, Smoke detector: 60sec
Power consumption Monitoring: 25VA max. approx
Alarm: 40VA max, approx
Maximum number of devices supported Spot type smoke detectors: 30/zone (max.150/panel)
Alarm bells: 15 (24VDC, 10mA/bell)
Location lamps: 5 (30V, 2W/lamp)  15(24V, 24mA/LED), 21 (24V, 15mA/LED)
Ambient temperature and humidity 0 to 40°C, 20 to 85% (RH)
Alarm input circuit loop resistance Less than 50Ω/Loop
End-of-Line resistor 10kΩ, 1/2W
Materials (enclosure) ABS resin with 94UL-V2 flammability rating
Color Off-white (Nohmi White): Approximating Munsell N8.7 or equivalent
Weight Approx. 3kg
Xem thêm