Module cho đầu báo thường 1 zone NOHMI FRRU004-CIZM4Module cho đầu báo thường 1 zone NOHMI FRRU004-CIZM4

– The Conventional Initiating Zone Module (FRRU004-CIZM4) is used to supervise the status of conventional initiating devices connected on an Initiating device circuit (IDC). The FRRU004-CIZM4 detects an alarm condition and reports to the Fire Alarm Control Panel (FACP). The FRRU004-CIZM4 module also supervises the initiating device wiring (A+, A-, B+, and B- wires) and wiring for the power supply connected to terminals 24+ and 24- to detect an open circuit. IDC wiring style is applicable to the NFPA Class B (Style B) & Class A (Style D). When the FRRU004-CIZM4 module detects an alarm, the module is latched until the system reset. When the FRRU004-CIZM4 module is used with Class A (Style D) wiring condition and detects an open circuit on wiring of the IDC and power supply connected to terminal 24+ and 24-, the module is also latched until the system reset.

– The FRRU004-CIZM4 module has one red LED for local indication of the statuses of module itself and its wiring. Normal conditions are indicated by flashing LED. Alarm condition is indicated by constant illumination. Open circuit condition is indicated by extinction.

Features

– One simple LED for status indication.

– NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC.

– NFPA Class A (Style D) and Class B (Style B) for IDC.

– Electronic address setting.

– Downsized unit.

– Easy installation.

Đặc tính kỹ thuật

Model   FRRU004-CIZM4
Rated voltage range of SLC input power (S+,S-) 22.0 to 24.0V
Maximum SLC 24 VDC standby current (S+,S-) 250µA
Maximum SLC 24 VDC alarm current (S+,S-) 1mA
Operating voltage of external power supply line (24+,24-) 24V
Output voltage range of IDC (A+,A-,B+,B-) 15.7 to 22.6V
Maximum module standby current of IDC 24 VDC (24+,24-) 8.5mA in Style B, 4.9mA in Style D
Maximum detector standby current of IDC 24 VDC (24+,24-) 2.4mA
Maximum module and detector alarm current of IDC 24 VDC (24+,24-) 50.0mA
Applicable IDC wiring style Class A (Style D), Class B (Style B)
Maximum wiring resistance of IDC 100Ω
Maximum wiring capacitance of IDC 1µF
End-of-line resistor for IDC in NFPA Style B wiring 5.1kΩ, 1/2W
Maximum alarm reset voltage 0V
Minimum alarm reset time 1.1 second
Operating temperature range 0°C to 49°C (32°F to 120°F)
Operating humidity range 0 to 93% (non-condensing)
Dimensions 106mm (4.17 inches) (H) × 106mm (4.17 inches) (W) × 29mm (1.14 inches) (D
Applicable electrical box for installation North American 64mm (2-1/2 inches) deep 2-gang box
Standard 4 inches square box 38mm (1-1/2 inch) deep box