Module giám sát lối vào NOHMI FRRU004-MCM
– The Miniature Contact Module (FRRU004-MCM) is used to monitor the contact status of an initiating device that contains a normally open contact.
– The FRRU004-MCM can be programmed in the panel to supervise either a Normally-open or Normally-closed contact on the Fire Alarm Control Panel (FACP). When the Normally-open contact is selected, and the contact is closed, the FRRU004-MCM reports its condition to FACP. Likewise when the Normally-closed contact is set to a supervising condition, and the contact is opened, the FRRU004-MCM reports its condition to FACP. FRRU004-MCM supervises an open circuit of wiring connected to the terminal C and NO (NC) contact. The FRRU004-MCM is generally used to monitor pull stations and other devices where the module is installed in an electrical box or enclosure. The contact utilizes a terminal block that is covered in accordance with UL requirements to protect from inadvertent shorts and ground faults.
Features
– NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC.
– NFPA Class B (Style B) for IDC.
– Electronic address setting.
– Mini-sized unit.
– Easy installation.
Đặc tính kỹ thuật
Model | FRRU004-MCM |
Rated voltage range of SLC input power (S+,S-) | 22.0 to 24.0V |
Maximum SLC 24 VDC standby current (S+,S-) | 250µA |
Maximum SLC 24 VDC alarm current (S+,S-) | 250µA |
IDC input circuit wiring style | Class B (Style B) |
End-of-line resistor for IDC | 5.1kΩ, 1/2W |
Maximum wiring resistance of IDC | 100Ω |
Maximum wiring capacitance of IDC | 1µF |
Operating temperature range | 0°C to 49°C (32°F to 120°F) |
Operating humidity range | 0 to 93% (non-condensing) |
Dimensions | 65.5mm (2.58 inches) (H) × 59mm (2.32 inches) (W) × 24mm (0.94 inch) (D) |
Applicable electrical box for installation | North American 64mm (2-1/2 inches) deep single-gang box |